TECHNICAL BULLETIN
TS700/002
TS700 CONTROL PANEL
Menvier Technical Support have received queries regarding the facility to wire exit terminator
buttons per ward. The following will solve up to 2 exit terminator buttons. If you require more
then you will need to consider installing a TS790 / TS900 Control Panel.
The TS700 was developed several years ago and one of its limitations is that once a ward
has set, any unset wards will revert to timed exit. With this in mind it will be necessary to
change the setting modes for all part sets to timed exit and to set the exit time to 199 sec
(max).
Wiring
Any exit terminators fitted to the system will need to wired in parallel to the same zone.
Panel output 1 or 2 (switched -ve) must be programmed as zone mimic for the zone the exit
terminators are wired into. For example if the exit terminators are connected to zone 8,
program panel output (1 or 2) to type 47 (zone 8 mimic).
The programmed output needs to be wired through a 2K2 resistor to a zone that will be used
as the exit terminator for a different ward (e.g. zone 7).
Zones 7 & 8 must be programmed to the type ET (exit terminator) and assigned to the
respective ward.
Operation
When either exit terminator button is pressed the output activates, this then activates the
other zone programmed as exit terminator, which will set the area that is in exit mode.
NOTE
The settle time should be set to 5 seconds or higher and the exit terminator must not be
pressed and held as this may cause a set fail condition.