Entry Time (key
5
)
When the entry procedure is initiated, the Entry Timer is started and the display counts down
the remaining time. If a valid user passcode is not entered when the timer reaches zero,
a full alarm tone is generated from the internal sounders only and the timer is restarted. If
a valid user passcode is not entered when the timer reaches zero for the second time the
external sounder is activated. The timer may be set between 1 and 255 seconds.
1 Ensure that the "ENGR. OPTION -" is displayed. Press
5
to select the Entry Time option.
2 Enter the timer setting using the number keys e.g., to set the Entry Time to 25 seconds,
enter "025"
3 When completed, press
[
to accept, a two tone acceptance tone will be heard.
Bell Duration Time (key
6
)
This timer controls the duration of the external sounder when the system is triggered into a
full alarm condition. The timer may be set between 000 and 255 minutes, when the timer
is set to "000" the output becomes continuous.
1 Ensure that the "ENGR. OPTION -" is displayed. Press
6
to select the Bell Duration Time
option.
2 Enter the timer setting using the number keys e.g., to set the Bell Duration Time to 10
minutes, enter "010"
3 When completed, press
[
to accept, a two tone acceptance tone will be heard.
Change Engineer's Passcode (key
7
)
The factory default engineer's passcode is set to 1 2 3 4, but the installation engineer should
change this to their own personal 4 digit passcode as follows:
1 Ensure that the "ENGR. OPTION -" is displayed. Press
7
to select the Change Engineer's
Passcode option.
2 Enter the new passcode using the number keys e.g., to set the passcode to 2580
enter "2580"
3 When completed, press
[
to accept, a two tone sound indicates acceptance, a
single low tone sound indicates that the new passcode was not accepted. Repeat
the procedure, trying a different passcode.
Remote Reset Number (key
8
)
The "Engineer Reset" option may be overridden by the user, operating the "Remote Reset"
facility. If an alarm is generated the system will respond with a four digit "seed" code which
the user quotes to the alarm company. The "seed" code is then entered into a decoder
and a unique "Remote Reset" code is generated. This is passed back to the user and, on
entering the "Remote Reset" code, the system will reset.
Programming TSD402 Installation Manual
24